ezeio2:scriptref:doalarm

Trigger activation of an alarm.

Description

DoAlarm( alarmno, force, dparam, iparam1, iparam2, text, ... )

This command will change the state of an alarm into active and trigger any alarm actions accordingly. If the force parameter is 0/false and the alarm is already in active state, the actions are not re-triggered.

If the alarm is not active, the restore logic and holdoff will determine if/when the restore actions will execute.

Parameters

alarmno The alarm number
force If set to TRUE/1, the actions will be run even if the alarm was already in alarm state
dparam A user-defined float value (accessed by [P2] in templates
iparam1 A user-defined integer value [P3]
iparam2 A user-defined integer value [P4]
text User defined formatted text to include in the alarm message [TEXT]

Return value

Returns the previous state of the alarm. 1=alarm was already active. 0=alarm was not active.

Example usage

   new t = 99;
   DoAlarm(4, 0, 1.1, 200, 333, "Too hot! Temp=%d degrees!", t);

NOTE: First appeared in firmware 24060601

  • ezeio2/scriptref/doalarm.txt
  • Last modified: 2024-06-07 19:34
  • by andreh