ezeio2:drivers:doc:ee_temp_rh

Description

This driver is design to allow communication with E+E Elektronik's EE210 humidity sensor, via the ezeio MkII's Modbus serial port. The driver may be compatible with other E+E humidity sensors with Modbus connectivity, such as EE072, EE150, and EE211.


Name - The name is up to the user. Our suggestion is to choose a naming convention that makes the viewing the device list intuitive. Such as referring to the sensor and/or application. Keep the name short as it will be combined with the register name to create the default “Field” name (if added to “Fields”)

Active Check box - Check this box and “Save changes” to run the driver. The driver program can be suspended by unchecking the box and clicking on “Save changes”.

User Notes - This space can be used to store information specific to the device and your application, such as: location, wiring, scaling, etc.

eze System Notes - In this space we provide: wiring instructions, product image, product details.


Modbus Address - Enter the devices unique Modbus address (device ID)

Device model Units - Select “Metric” or “Imperial” as your preferred units of measure.


Device Status

Driver info - Typically this is the name from the program file

Driver updated/version - Date loaded or updated and the version of the driver

Battery & Signal - Signal indicates the progress through the script. If driver fails to operate, signal number indicates progress

Driver status - Color and text of status bubbles give a quick visual reference of Communication, Operation, and Application

Communication - Com count indicates number of successful and unsuccessful data packets received


Available registers

  1. Temperature (Celsius) - Ambient temperature in Celsius.
  2. Temperature (Fahrenheit) - Ambient temperature in Fahrenheit.
  3. Relative Humidity (%) - Percentage of ambient humidity (moisture).
  4. Water Vapor Partial Pressure (milibar) - Pressure (in millibar) at which the water vapor in the air condenses to liquid.
  5. Water Vapor Partial Pressure (psi) - Pressure (in psi) at which the water vapor in the air condenses to liquid.
  6. Dew point Temperature (Celsius) - Temperature (in Celsius) at which the water vapor in the air condenses to liquid.
  7. Dew point Temperature (Fahrenheit) - Temperature (in Fahrenheit) at which the water vapor in the air condenses to liquid.
  8. Wet bulb (Celsius) - Corrected temperature (in Celsius) calculating the effect of evaporated cooling based on relative humidity.
  9. Wet bulb (Fahrenheit) - Corrected temperature (in Fahrenheit) calculating the effect of evaporated cooling based on relative humidity.
  10. Absolute humidity (grams per cubic meter) - Mass of water per volume (cubic meter).
  11. Absolute humidity (grams per cubic foot) - Mass of water per volume (cubic foot).
  12. Mixing ratio (grams per kilogram) - Ratio of grams of water to a kilogram of dry air
  13. Mixing ratio (grams per pound) - Ratio of grams of water to a pound of dry air.
  14. Specific enthalpy (kilojoules per kilograms) - The amount of energy (in Joules) per kilogram.
  15. Specific enthalpy (BTU per pound) - The amount of energy (in BTU's) per pound.
  16. Frost point temperature (Celsius) - Temperature (in Celsius) at which the water vapor in the air will freeze.
  17. Frost point temperature (Fahrenheit) - Temperature (in Fahrenheit) at which the water vapor in the air will freeze.
  • ezeio2/drivers/doc/ee_temp_rh.txt
  • Last modified: 2024-05-23 21:57
  • by johpar