Grundfos pump CIM200
Manufacturer: Grundfos
Product: CIM/CIU 200
Model: CIM200
Class: MODBUS
Updated: 2023-11-13
[ CLICK HERE FOR MORE INFORMATION ]
Registers
# | Name | Unit | Description |
---|---|---|---|
1 | Head | bar | Actual system head/pressure |
2 | VolumeFlow | m³/h | Actual system flow |
3 | RelativePerformance | % | Performance relative to maximum performance |
4 | Speed | rpm | Motor speed |
5 | Frequency | Hz | Actual control signal applied to motor |
6 | DigitalInput | Logical value of external digital input signals | |
7 | DigitalOutput | Logical value of external digital output signals | |
8 | ActualSetpoint | % | Actual setpoint: Open loop: % of nominal frequency. Closed loop: % of sensor maximum |
9 | MotorCurrent | A | Actual motor current. |
10 | DCLinkVoltage | V | Frequency converter DC-Link voltage |
11 | MotorVoltage | V | Motor Voltage |
12 | Power | W | Total power consumption of the system |
13 | RemoteFlow | m³/h | Measured flow at external sensor |
14 | InletPressure | bar | System inlet pressure (relative to atmospheric pressure) |
15 | RemotePressure | bar | Measured pressure at external sensor (relative to atmospheric pressure) |
16 | Level | m | Tank level |
17 | PowerElectronicTemp | °C | Temperature in frequency converter |
18 | MotorTemp | °C | Motor winding temperature |
19 | RemoteTemp | °C | Temperature at external sensor |
20 | ElectronicTemp | °C | E-pump electronics temperature |
21 | PumpLiquidTemp | °C | Pumped-liquid temperature |
22 | BearingTempDE | °C | Bearing temperature, drive end |
23 | BearingTempNDE | °C | Bearing temperature, non-drive end. |
24 | AuxSensorInput | % | Auxiliary sensor input. |
25 | SpecificEnergyConsumption | Wh/m³ | Specific energy consumption |
26 | OperationTime | h | Total operating time of the system |
27 | TotalPoweredTime | h | Total power-on time of the system |
28 | Torque | Nm | Motor torque. |
29 | Energy | kWh | Total energy consumption of the system. |
30 | NumberOfStarts | Number of times the E-pump has been started | |
31 | RemoteTemp2 | °C | Temperature at external temperature sensor 2 |
32 | UserSetpoint | % | User-selected setpoint. Open loop: % of nominal frequency. Closed loop: % of setpoint range |
33 | Diffpressure | bar | Pressure between pump flanges |
34 | OutletPressure | bar | Pressure at pump outlet |
35 | RemotePressure2 | bar | Pressure measured by external sensor 2. |
36 | LoadPercent | % | Motor current in percent of rated motor current. |
37 | PumpUnixRtc | Pump time and date in UNIX format | |
38 | MaxFlowLimit | m³/h | Actual maximum flow limit |
39 | RemoteDiffTemp | °C | Remote differential temperature |
40 | InletDiffPressure | bar | Inlet differential pressure. |
41 | OutletDiffPressure | bar | Outlet differential pressure |
42 | RemoteDiffPressure | bar | Remote differential pressure |
43 | StorageTankLevel | m | Storage tank level. |
44 | AmbientTemp | °C | Ambient temperature |
45 | HeatEnergyCounter | kWh | Total accumulated heat energy in pump life time |
46 | HeatPower | W | Actual heat power |
47 | HeatDiffTemp | °C | Differential temperature between forward and return pipe used for heat calculation |
48 | Volume | m³ | Totally pumped volume |
49 | HeatEnergyCounter2 | kWh | Total accumulated heat energy in pump lifetime |
50 | Volume2 | m³ | Totally pumped volume |
51 | Status | Status flags | |
52 | ProcessFeedback | % | |
53 | ControlMode | ||
54 | OperationMode | ||
55 | AlarmCode | ||
56 | WarningCode | ||
57 | MonthsToBearingService | ||
58 | BearingServiceType | ||
59 | DriveState | ||
60 | FeedbackSensorUnit | ||
61 | FeedbackSensorMin | ||
62 | FeedbackSensorMax | ||
63 | NomFrequency | ||
64 | MinFrequency | % | |
65 | MaxFrequency | % | |
66 | SetPointMin | % | |
67 | SetPointMax | % | |
68 | FlowEstimationState | ||
69 | Run | ||
70 | Running | ||
71 | Setpoint write | % | |
72 | Control mode write | . | |
73 | Operation mode write | . |
Notes
Modbus/RTU interface card for Grundfos pumps.