Senix ToughSonic 14
Manufacturer: Senix
Product: ToughSonic 14
Model: TSPC-N1S1-485A
Class: MODBUS
Updated: 2024-06-27
[ CLICK HERE FOR MORE INFORMATION ]
Senix ToughSonic 14 sensor
Description
This driver is design to allow communication with the Senix ThoughSonic 14, ultrasonic tank level sensor via Modbus RTU.
Settings (center panel)
Name - The name is up to the user. Our suggestion is to choose a naming convention that makes the viewing the device list intuitive. Such as referring to the sensor and/or application. Keep the name short as it will be combined with the register name to create the default “Field” name (if added to “Fields”)
Active Check box - Check this box and “Save changes” to run the driver. The driver program can be suspended by unchecking the box and clicking on “Save changes”.
User Notes - This space can be used to store information specific to the device and your application, such as: location, wiring, scaling, etc.
eze System Notes - In this space we provide: wiring instructions, product image, product details.
Modbus address - Enter Device I.D. (Modbus address). This address must be unique on the bus.
Registers
# | Name | Unit | Description |
---|---|---|---|
1 | Distance | in | Distance, imperial, unfiltered |
2 | Distance | m | Distance, metric, unfiltered |
3 | Distance filtered | in | Distance, imperial, filtered |
4 | Distance filtered | m | Distance, metric, filtered |
5 | Cycle count | Cycle count 0-255 |
Notes
Ultrasonic range meter, 4in to 14ft (10.2cm to 4.2m), 12 degree beam Sensor GRAY -> Modbus D0 Sensor YELLOW -> Modbus D1 Sensor BLUE -> 0V / gnd Sensor BROWN -> +DC (10-30V) Sensor default is 9600bps/N81, address 1