Thermostat logic
Manufacturer: eze System
Product:
Model:
Class: CORE
Updated: 2025-08-12
Registers
# | Name | Unit | Description |
---|---|---|---|
1 | Actual temperature | ° | |
2 | Cooling Setpoint | ° | |
3 | Heating Setpoint | ° | |
4 | Mode | . | |
5 | Stay/Away | . | |
6 | Override timer | s | |
7 | Fan | . | |
8 | Cooling | . | |
9 | Heating | . | |
10 | Running time | s | |
11 | Stopped time | s | |
12 | Total runtime | s | |
13 | System fault | . |
Notes
Thermostat logic for single stage heat/cool system. Configure the temperature sensor expression to any temperature field or register. The Stay condition sets the Stay/Away mode (optional). The Fault condition is checked 75 seconds after start. If true it will latch register 13 on and system stops. Cycling time allows multiple instances to run one-at-a-time. If cycling time is non-zero, each instance will only run a max of that time. The instance that has been stopped for the longest will run next. User must set override timer manually before override is possible. Fan will be active an additional 30 seconds after heat/cool shuts off.