Siemens RWF55 Temp/Pressure controller
Manufacturer: Siemens
Product: RWF55.5
Model:
Class: MODBUS
Updated: 2025-02-20
[ CLICK HERE FOR MORE INFORMATION ]
Registers
# | Name | Unit | Description |
---|---|---|---|
1 | Analog input InP1 | ||
2 | Analog input InP2 | ||
3 | Analog input InP3 | ||
4 | Actual setpoint | ||
5 | Setpoint 1 | ||
6 | Setpoint 2 | ||
7 | Analog input InP3 (unfiltered) | ||
8 | Actual angularpositioning | ||
9 | Burner alarm | ||
10 | Outputs and states | ||
11 | Binary signals and hardware detection | ||
12 | Proportional range 1 | ||
13 | Derivative action time | ||
14 | Integral action time | ||
15 | Dead band | ||
16 | Controlling element running time | ||
17 | Switch-on threshold | ||
18 | Switch-off threshold down | ||
19 | Switch-off threshold up | ||
20 | Switch-on threshold (cooling) | ||
21 | Switch-off threshold down (cooling) | ||
22 | Switch-off threshold up (cooling) | ||
23 | Reaction threshold | ||
24 | Outside temperature 1 | °C | |
25 | Boiler temperature 1 | °C | |
26 | Outside temperature 2 | °C | |
27 | Boiler temperature 2 | °C | |
28 | Start of display input 1 | ||
29 | End of display input 1 | ||
30 | Start value input 2 | ||
31 | End value input 2 | ||
32 | Start of setpoint limitation | ||
33 | End of setpoint limitation | ||
34 | Offset input E1 | ||
35 | Offset input E2 | ||
36 | Offset input E3 | ||
37 | Ramp function | ||
38 | Ramp slope | ||
39 | Tolerance band ramp | ||
40 | Limit value | ||
41 | Remote Detection Timer | ||
42 | Filter constant input 1 | ||
43 | Filter constant input 2 | ||
44 | Filter constant input 3 | ||
45 | Lower working range limit | ||
46 | Upper working range limit | ||
47 | Alarm relay function | ||
48 | Alarm relay limit value (limit value alarm) | ||
49 | Alarm relay hysteresis | ||
50 | Activation remote operation * | ||
51 | Controller OFF in remote setpoint ** | ||
52 | Switch-on threshold remote | ||
53 | Switch-off threshold down remote | ||
54 | Switch-off threshold up remote | ||
55 | Setpoint remote | ||
56 | Burner release remote operation | ||
57 | Relay K2 remote operation | ||
58 | Relay K3 remote operation | ||
59 | Relay K6 remote operation | ||
60 | Step-by-step control remote operation | ||
61 | Angular positioning output remote operation | ||
62 | Switch-on threshold remote (cooling) | ||
63 | Switch-off threshold down remote (cooling) | ||
64 | Switch-off threshold up remote (cooling) |
Notes
Compact universal controller optimized for temperature and pressure control in connection with modulating or multistage burners and air conditioning systems. Connect: ezeio D0 -> R- ezeio D1 -> R+ ezeio 0V -> C4 Set baud rate under Conf->IntF->r485->bdrt 1 = 9600 2 = 19200 Set address under Conf->IntF->r485->Adr