ezeio2:driverdetail

Manufacturer: Siemens Combustion Controls
Product: LMV5
Model:
Class: MODBUS
Updated: 2024-08-07

[ CLICK HERE FOR MORE INFORMATION ]


Registers

#NameUnitDescription
1PhaseStage of operation
2Position of currently active fuel actuator°Fuel servo position
3Position of air actuator°Air servo position
4Position of auxiliary actuator 1°
5Position of auxiliary actuator 2°
6Position of auxiliary actuator 3°
7Manipulated variable for variable speed drive%
8Current output%Load
9Current setpoint - temperature°FSetpoint
10Current setpoint - pressurepsiSetpoint
11Actual value - temperature°FActual
12Actual value - pressurepsiActual
13Flame signal%Flame Signal
14Current fuel throughput0..65534Flow meter reading
15Current O2 value (LMV52...)%Exhaust O2%
16Startup counter total#total number of start ups
17Hours run counterhRun hours
18Current error: Error codehex
19Current error: Diagnostic codehex
20Current error: Error class.
21Current error: Error phase.
22Temperature limiter OFF threshold°FCold plant start temperature to see what boiler internal water temperature is currently
23Supply air temperature (LMV52...)°FAmbient Air Temp
24Flue gas temperature (LMV52...)°FFlue gas temperature
25Combustion efficiency (LMV52...)%
26Inputs (bits).
27Outputs (bits).
28Operating mode with load controller.Load controller type
29Selection of manual or automatic operation.Auto, Manual, Manual OFF
30Operating mode in Remote mode. Auto, Remote ON, Remote OFF.
31External setpoint W3 Temperature°FRemote Setpoint
32External setpoint W3 PressurepsiRemote Setpoint
33Predefined output mod. / multistage%
34Setpoint W1 Temperature°FLocal Setpoint W1
35Setpoint W1 PressurepsiLocal Setpoint W1
36Setpoint W2 Temperature°FLocal Setpoint W2
37Setpoint W2 PressurepsiLocal Setpoint W2
38Startup counter gas (adjustable to zero only)#
39Startup counter oil (adjustable to zero only)#
40Startup counter total (adjustable to zero only)#
41Startup counter total (read only)#
42Fuel volume gasft³
43Fuel volume oilgal
44Number of lockouts#
45Extra temperature sensor (from AZL5... version V4.10 or later)°F
46Min-output gas%
47Max-output gas%
48Min-output oil%
49Max-output oil%
50Load limitation enduser (modulating)%
51Load limitation enduser (multistage).
52Temperature limiter switching differential ON%Cold Plant Active
53Type of fuel.

Notes

The LMV5 Burner / Boiler Management System (BMS) is ideally suited for use with steam
boilers, hot water boilers, thermal fluid heaters, and industrial burners.

Connect Omron converter :
(7) SG -> ezeio common
(9) SDA -> ezeio D0
(12) SDB -> ezeio D1

  • ezeio2/driverdetail.txt
  • Last modified: 2024-05-07 23:25
  • by andreh