Siemens LMV5 BMS
Manufacturer: Siemens Combustion Controls
Product: LMV5
Model:
Class: MODBUS
Updated: 2024-11-15
[ CLICK HERE FOR MORE INFORMATION ]
Registers
# | Name | Unit | Description |
---|---|---|---|
1 | Phase | Stage of operation | |
2 | Position of currently active fuel actuator | ° | Fuel servo position |
3 | Position of air actuator | ° | Air servo position |
4 | Position of auxiliary actuator 1 | ° | |
5 | Position of auxiliary actuator 2 | ° | |
6 | Position of auxiliary actuator 3 | ° | |
7 | Manipulated variable for variable speed drive | % | |
8 | Current output | % | Load |
9 | Current setpoint - temperature | °F | Setpoint |
10 | Current setpoint - pressure | psi | Setpoint |
11 | Actual value - temperature | °F | Actual |
12 | Actual value - pressure | psi | Actual |
13 | Flame signal | % | Flame Signal |
14 | Current fuel throughput | 0..65534 | Flow meter reading |
15 | Current O2 value (LMV52...) | % | Exhaust O2% |
16 | Startup counter total | # | total number of start ups |
17 | Hours run counter | h | Run hours |
18 | Current error: Error code | hex | |
19 | Current error: Diagnostic code | hex | |
20 | Current error: Error class | . | |
21 | Current error: Error phase | . | |
22 | Temperature limiter OFF threshold | °F | Cold plant start temperature to see what boiler internal water temperature is currently |
23 | Supply air temperature (LMV52...) | °F | Ambient Air Temp |
24 | Flue gas temperature (LMV52...) | °F | Flue gas temperature |
25 | Combustion efficiency (LMV52...) | % | |
26 | Inputs (bits) | . | |
27 | Outputs (bits) | . | |
28 | Operating mode with load controller | . | Load controller type |
29 | Selection of manual or automatic operation | . | Auto, Manual, Manual OFF |
30 | Operating mode in Remote mode. Auto, Remote ON, Remote OFF | . | |
31 | External setpoint W3 Temperature | °F | Remote Setpoint |
32 | External setpoint W3 Pressure | psi | Remote Setpoint |
33 | Predefined output mod. / multistage | % | |
34 | Setpoint W1 Temperature | °F | Local Setpoint W1 |
35 | Setpoint W1 Pressure | psi | Local Setpoint W1 |
36 | Setpoint W2 Temperature | °F | Local Setpoint W2 |
37 | Setpoint W2 Pressure | psi | Local Setpoint W2 |
38 | Startup counter gas (adjustable to zero only) | # | |
39 | Startup counter oil (adjustable to zero only) | # | |
40 | Startup counter total (adjustable to zero only) | # | |
41 | Startup counter total (read only) | # | |
42 | Fuel volume gas | ft³ | |
43 | Fuel volume oil | gal | |
44 | Number of lockouts | # | |
45 | Extra temperature sensor (from AZL5... version V4.10 or later) | °F | |
46 | Min-output gas | % | |
47 | Max-output gas | % | |
48 | Min-output oil | % | |
49 | Max-output oil | % | |
50 | Load limitation enduser (modulating) | % | |
51 | Load limitation enduser (multistage) | . | |
52 | Temperature limiter switching differential ON | % | Cold Plant Active |
53 | Type of fuel | . |
Notes
The LMV5 Burner / Boiler Management System (BMS) is ideally suited for use with steam boilers, hot water boilers, thermal fluid heaters, and industrial burners. Connect Omron converter : (7) SG -> ezeio common (9) SDA -> ezeio D0 (12) SDB -> ezeio D1