Manufacturer: Generac
Product: PowerZone PRO
Model: PowerZone PRO
Class: MODBUS
Updated: 2024-07-02

[ CLICK HERE FOR MORE INFORMATION ]


Registers

#NameUnitDescription
1Remote annunciator.
2DI Results 106.
3DOF Results 112.
4113.
5114.
6GEN VOLTAGE AN Vx10V
7GEN VOLTAGE BN Vx10V
8GEN VOLTAGE CN Vx10V
9GEN VOLTAGE LN AVG Vx10V
10GEN VOLTAGE AB Vx10V
11GEN VOLTAGE BC Vx10V
12GEN VOLTAGE CA Vx10V
13GEN VOLTAGE LL AVG Vx10V
14GEN CURRENT A Ax10A
15GEN CURRENT B Ax10A
16GEN CURRENT C Ax10A
17GEN CURRENT AVG Ax10A
18GEN CURRENT N Ax10A
19GEN APPARENT PWR LL TOTALkVA
20GEN REACTIVE PWR LL TOTALkVAr
21GEN PF LL AVG.
22AVR FIELD CURRENT/AVR SCR DELAY ANGLEA
23AVR EXCITATION VOLTAGE/FREQUENCYV
24GEN FREQ LL HZx10Hz
25RPM 1rpm
26BATT VOLTAGE Vx100V
27BATT CHARGER CURRENT 1A
28OIL TEMP 1°F
29OIL PRESS 1psi
30OIL PRESS 2psi
31COOLANT TEMP 1°F
32COOLANT TEMP 2°F
33COOLANT LEVEL ENGINE 1%
34GOVERNOR THROTTLE POSITION 1.
35AIR FUEL RATIO DUTY CYCLE 1.
36PRE CAT O2 SENSOR 1.
37INTAKE MANIFOLD AIR TEMP 1°F
38ENGINE_PERCENT_LOAD_AT_SPEED.
39ENGINE DESIRED SPEEDrpm
40BOOST_PRESS_POST_TURBO_1psi
41ENGINE_FUEL_DELIVERY_PRESSURE kPa
42DIESEL_FUEL_TEMP.
43DIESEL_FUEL_FLOW_RATE.
44DIESEL_FUEL_LEVEL_1%
45INTAKE AIR PRESSURE DELTA FILTER 1.
46INTAKE AIR PRESSURE .
47??? alarm_global_commands.
48alarm_globals.
49Engine_Hour_Nowh
50Engine_Status_Word.
51Genset_Status_Word.
52??? _maint_life_remaining.
53Engine_kW_Hours_NowkWh
54_o2_sensor.
55_gov_position.
56alarm_global.
57auto_off_manualValue
58battery_charger_currentA
59battery_voltage_vx100V
60def_level%
61fuel_level%
62fuel_pressurepsi
63gen_frequencyHz
64turbo_boost_pressurepsi
65intake_air_temperature°F
66kw_hourskWh
67gen_last_kwhrkWh
68last_run_hoursh
69oil_level%
70gen_total_kwkW
71gen_total_power_factor.
72rpm1rpm
73engine_hours_nowh
74system_status.
75battery_temperature.
76sync_angle.
77alarm_log_idx.
78event_log_idx.
79gen_switch_closedState
80_remote_startCommand

Notes

PowerZone PRO engine controller with communications gateway

Defaut address: 1  or  100
Default baud: 9600

RS-485 connection
B (Pin 14) to DO
A (Pin 12) to D1

DISCLAIMER:
This driver has not been fully validated by eze System.

  • ezeio2/driverdetail.txt
  • Last modified: 2024-05-07 23:25
  • by andreh