Smartpack S Charge controller

Manufacturer: Eltek
Product: Smartpack S
Model: Smartpack S
Class: MODBUS
Updated: 2024-10-10
[ CLICK HERE FOR MORE INFORMATION ]
Registers
| # | Name | Unit | Description |
|---|---|---|---|
| 1 | Battery Voltage (@ bus-bar) | V | |
| 2 | Battery Current | A | |
| 3 | Battery Temperature | °C | |
| 4 | Remaining Battery Capacity | Ah | |
| 5 | Battery Time left | min | |
| 6 | Load Current | A | |
| 7 | Load Voltage | V | |
| 8 | Rectifier Voltage | V | |
| 9 | Rectifier Current Nominal | A | |
| 10 | Mains Voltage Phase #1 | V | |
| 11 | Mains Voltage Phase #2 | V | |
| 12 | Mains Voltage Phase #3 | V | |
| 13 | Mains Current Phase #1 | A | |
| 14 | Mains Current Phase #2 | A | |
| 15 | Mains Current Phase #3 | A | |
| 16 | Mains Frequency | Hz | |
| 17 | Solar Current Total | A | |
| 18 | Major Alarm - Rectifiers in Alarm | . | |
| 19 | Minor Alarm – Rectifiers in Alarm | . | |
| 20 | Major Alarm – Any Battery Alarm | . | |
| 21 | Minor Alarm - Any Battery Alarm | . | |
| 22 | Battery State of Charge | ||
| 23 | Battery Utilized Life (battery life time) | Days | |
| 24 | Battery Health SOH (battery quality) | % | |
| 25 | Mains voltage phase 1 | V | |
| 26 | Mains current total (Measured Mains Monitor) | A | |
| 27 | Generator running minutes | min | |
| 28 | Fuel consumption | ? | |
| 29 | Battery cycle count | Cycles | |
| 30 | Depth of discharge | % | |
| 31 | Mains availability minutes | min | |
| 32 | Temperature 1.1 | °C | |
| 33 | Temperature 1.2 | °C | |
| 34 | Temperature 1.3 | °C | |
| 35 | Ground fault alarm | . | |
| 36 | Status | . | |
| 37 | LiIon Battery 1 Voltage | V | |
| 38 | LiIon Battery 1 Current | A | |
| 39 | LiIon Battery 1 Temp | °C | |
| 40 | LiIon Battery 1 SoC Ah | Ah | |
| 41 | LiIon Battery 1 SoC % | % | |
| 42 | LiIon Battery 1 Env Temp | °C | |
| 43 | LiIon Battery 1 Warning | . | |
| 44 | LiIon Battery 1 Protection | . | |
| 45 | LiIon Battery 1 Status | . | |
| 46 | LiIon Battery 2 Voltage | V | |
| 47 | LiIon Battery 2 Current | A | |
| 48 | LiIon Battery 2 Temp | °C | |
| 49 | LiIon Battery 2 SoC Ah | Ah | |
| 50 | LiIon Battery 2 SoC % | % | |
| 51 | LiIon Battery 2 Env Temp | °C | |
| 52 | LiIon Battery 2 Warning | . | |
| 53 | LiIon Battery 2 Protection | . | |
| 54 | LiIon Battery 2 Status | . | |
| 55 | LiIon Battery 3 Voltage | V | |
| 56 | LiIon Battery 3 Current | A | |
| 57 | LiIon Battery 3 Temp | °C | |
| 58 | LiIon Battery 3 SoC Ah | Ah | |
| 59 | LiIon Battery 3 SoC % | % | |
| 60 | LiIon Battery 3 Env Temp | °C | |
| 61 | LiIon Battery 3 Warning | . | |
| 62 | LiIon Battery 3 Protection | . | |
| 63 | LiIon Battery 3 Status | . |
Notes
Telecom DC power system Battery charge controller Modbus RTU / UART settings or IP configuration needs to be set on-site via built in configuration interface. See Smartpack manual. Default IP: 192.168.10.20 Default Login: admin Default Password: admin RS485 connections Connect Pin #1 to ezeio D1 Connect Pin #2 to ezeio D0 Connect common to ezeio ground