Bes-Tech DigiRTU
Manufacturer: Bes-Tech
Product: Digi-RTU
Model:
Class: MODBUS
Updated: 2023-11-13
[ CLICK HERE FOR MORE INFORMATION ]
Registers
# | Name | Unit | Description |
---|---|---|---|
1 | Indoor fan call from T-stat or BAS | . | |
2 | Cooling call from T-stat or BAS | . | |
3 | Heating call from T-stat or BAS | . | |
4 | Outside air temperature (Digi-RTU sensor) | °F | |
5 | Outside air relative humidity (Digi-RTU sensor) | % | |
6 | Supply air temperature (Digi-RTU sensor) | °F | |
7 | Return air CO2 concentration Digi-RTU sensor) | ppm | |
8 | Return air or room air temperature (Digi-RTU sensor) | °F | |
9 | Return air relative humidity (Digi-RTU sensor) | % | |
10 | Fan command to fan contactor or VFD | . | |
11 | Power exhaust fan command | . | |
12 | On/off command to the first compressor in the first circuit | . | |
13 | On/off command to the first compressor in the second circuit | . | |
14 | On/off command to the second compressor in the first circuit | . | |
15 | On/off command to the second compressor in the second circuit | . | |
16 | On/off command to the first stage heater | . | |
17 | On/off command to the second stage heater | . | |
18 | Outside air damper command | % | |
19 | Supply fan speed command | Hz | |
20 | Supply fan speed feedback | Hz | |
21 | Supply fan power | kW | |
22 | Compressor speed command | Hz | |
23 | Compressor speed feedback for the first compressor in the first circuit | Hz | |
24 | Compressor power for the first compressor in the first circuit | kW | |
25 | Compressor speed feedback for the first compressor in the second circuit | Hz | |
26 | Compressor power for the first compressor in the second circuit | kW | |
27 | Overrride to the indoor fan on/off | . | |
28 | Override to the first stage heater on/off | . | |
29 | Override to the second stage heater on/off | . | |
30 | Overrride to the first compressor in the first circuit on/off | . | |
31 | Overrride to the first compressor in the second circuit on/off | . | |
32 | Overrride to the second compressor in the first circuit on/off | . | |
33 | Overrride to the second compressor in the second circuit on/off | . | |
34 | Overrride to the supply fan speed | . | |
35 | Override to the compressor speed | . | |
36 | Override to the outside air damper position | . | |
37 | Digi-RTU ID for Modbus communication with BAS | . | |
38 | Activate the new setting/address | . | |
39 | System type (RTU or HP) | . | |
40 | System configuration: 1/1; 1/2; 2/2; 2/3; and 2/4 | . | |
41 | Stacked or entwined | . | |
42 | Economizer enbaled or disabled | . | |
43 | Heat pump reversing valve type | . | |
44 | Number of compressor VFDs | . | |
45 | VFD brand for supply fan | . | |
46 | Maximum output to supply fan VFD | mV | |
47 | VFD speed corresponding to the maximum input to the VFD | Hz | |
48 | Minimum output to supply fan VFD | mV | |
49 | VFD speed corresponding to the minimum input to the VFD | Hz | |
50 | Fan only speed setpoint | Hz | |
51 | VFD brand for the first compressor VFD | . | |
52 | VFD brand for the second compressor VFD | . | |
53 | Compressor VFD maximum output | mV | |
54 | Compressor VFD speed corresponding to the maximum output | Hz | |
55 | Compressor VFD minimum output | mV | |
56 | Compressor VFD speed corresponding to the minimum output | Hz | |
57 | Compressor VFD minimum speed limit | Hz | |
58 | Supply air temperature setpoint for cooling | °F | |
59 | Supply air temperature setpoint for economizer operation | °F | |
60 | Supply air temperature setpoint for heating | °F | |
61 | Return air temperature low limit for cooling | °F | |
62 | Lock out outside air temperature for compressors | °F | |
63 | Economizer high outside air temperature limit | °F | |
64 | Economizer low outside air temperature limit | °F | |
65 | Enthalpy economizer outside air enthalpy cutoff value | . | |
66 | Minimum output to the outside air damper | mV | |
67 | Maximum output to the outside air damper | mV | |
68 | Minimum outside air damper position | % | |
69 | Return air temeprature sensor type | . | |
70 | Supply air temperature sensor type | . | |
71 | Outside air temeprature sensor type | . | |
72 | Communication faults | . | |
73 | Economizer fault | . | |
74 | Heating fault | . | |
75 | Supply fan fault | . | |
76 | Compressor fault | . | |
77 | Condensor fault | . | |
78 | Evaporator fault | . | |
79 | Low charge fault | . | |
80 | Temperature sensor fault | . | |
81 | CO2 sensor fault | . |
Notes
The Digi-RTU is a Heating, Ventilation, and Air Conditioning (HVAC) rooftop unit control kit that is both a demand management and energy usage device. It is designed to improve the energy efficiency and demand requirements of a rooftop unit as well as solve the humidity, common noise, and frequent on/off issues of a rooftop unit through modulating the capacity of a rooftop unit to match the cooling or heating space requirements. Connect R25/+/Red -> ezeio D1 R25/-/Black -> ezeio D0 R25/0/White -> ezeio 0V/gnd