ezeio2:driverdetail

Manufacturer: Sensecap
Product: S-pH-01
Model: version 2
Class: MODBUS
Updated: 2024-06-27

[ CLICK HERE FOR MORE INFORMATION ]


Description

This driver is design to allow communication with the Sensecap S-pH-01, pH sensor via Modbus RTU.


Name - The name is up to the user. Our suggestion is to choose a naming convention that makes the viewing the device list intuitive. Such as referring to the sensor and/or application. Keep the name short as it will be combined with the register name to create the default “Field” name (if added to “Fields”)

Active Check box - Check this box and “Save changes” to run the driver. The driver program can be suspended by unchecking the box and clicking on “Save changes”.

User Notes - This space can be used to store information specific to the device and your application, such as: location, wiring, scaling, etc.

eze System Notes - In this space we provide: wiring instructions, product image, product details.


Modbus address - Enter Device I.D. (Modbus address). This address must be unique on the bus.

Registers

#NameUnitDescription
1Temperature°CTemperature in Celsius
2pHpHpH 0-14
3Temp compensate.Select temp sensor option. (0): External, (1): Disabled, (2): Internal
4Calibration 4.01pHpH
5Calibration 7.00pHpH
6Calibration 10.01pHpH
7Calibrate 4/7/10.During calibration, write the respective pH calibration solution number to this register

Notes

pH sensor

Connect;
Sensor RED -> ezeio +V
Sensor BLACK -> ezeio 0V/gnd
Sensor YELLOW -> ezeio D0
Sensor WHITE -> ezeio D1

To calibrate, put sensor in calibration liquid. 
Then set register 7 to 4/7/10 to calibrate.

  • ezeio2/driverdetail.txt
  • Last modified: 2024-05-07 23:25
  • by andreh