Generac ATS X
Manufacturer: Generac
Product: TX series
Model: TX611
Class: MODBUS
Updated: 2024-09-06
[ CLICK HERE FOR MORE INFORMATION ]
Registers
# | Name | Unit | Description |
---|---|---|---|
1 | ATS Status | . | |
2 | ATS Timer | s | |
3 | Contactor status | . | |
4 | S1 Engine status | . | |
5 | S1 Status Timer | s | |
6 | S2 Engine status | . | |
7 | S2 Status timer | s | |
8 | ATS test status | . | |
9 | Exercise timer | s | |
10 | ATS TVSS status | s | |
11 | S1 AB voltage | V | |
12 | S1 BC voltage | V | |
13 | S1 AC voltage | V | |
14 | S2 AB voltage | V | |
15 | S2 BC voltage | V | |
16 | S2 AC voltage | V | |
17 | Current A | A | |
18 | Current B | A | |
19 | Current C | A | |
20 | Current N | A | |
21 | S1 Power | kW | |
22 | S2 Power | kW | |
23 | S1 Energy | kWh | |
24 | S2 Energy | kWh | |
25 | S1 Freqency | Hz | |
26 | S2 Freqency | Hz | |
27 | Temperaure | °C | |
28 | Humidity | % |
Notes
Generat Automatic Transfer Switch TX Connect: J13:1 B+ -> ezeio D0 J13:2 A- -> ezeio D1 J13:3 COM -> ezeio GND Note: Modbus comms must be "Enabled" via HMI menu. Settings > RS485 > Enable Device ID# 240 Default Baud rate 9600 default, 19,200 alternate. Use HMI menu to change. Settings > RS485 > Baud > speed