ezeio2:driverdetail

Manufacturer: Monnit
Product: Serial Modbus Gateway
Model: ALTA
Class: MODBUS
Updated: 2024-06-27

[ CLICK HERE FOR MORE INFORMATION ]


Description

This driver is design to connect a Monnit Gateway via Modbus. The Monnit gateway supports multiple wireless devices. Additional eze System drivers are needed for the individual wireless devices.


Name - The name is up to the user. Our suggestion is to choose a naming convention that makes the viewing the device list intuitive. Such as referring to the sensor and/or application. Keep the name short as it will be combined with the register name to create the default “Field” name (if added to “Fields”)

Active Check box - Check this box and “Save changes” to run the driver. The driver program can be suspended by unchecking the box and clicking on “Save changes”.

User Notes - This space can be used to store information specific to the device and your application, such as: location, wiring, scaling, etc.

eze System Notes - In this space we provide: wiring instructions, product image, product details.


Modbus address - Enter Device I.D. (Modbus address). Default address is 95. This address must be unique on the bus.

Registers

#NameUnitDescription
1Gateway serial.Unique serial number
2Devices (Active).Number of registered sensors active
3Devices (Configured).Number of registered sensors configured to operate through the gateway
4Operating channel.Wireless channel in use 0-25
5Uptimes
6Active.
7Full reset.
8Network reset.

Notes

Gateway for connecting Monnit wireless devices

Connect:
ezeio D0 -> Gateway D- (green)
ezeio D1 -> Gateway D+ (orange)
ezeio +V -> Gateway V+ (red)
ezeio 0V -> Gateway GND (black)

Make sure gateway "SELECT" jumper is OFF.
Gateway factory defaults to 19200/N/8/1
Default address 95

  • ezeio2/driverdetail.txt
  • Last modified: 2024-05-07 23:25
  • by andreh