Monnit Modbus Gateway
Manufacturer: Monnit
Product: Serial Modbus Gateway
Model: ALTA
Class: MODBUS
Updated: 2024-06-27
[ CLICK HERE FOR MORE INFORMATION ]
Monnit Modbus Gateway driver
Description
This driver is design to connect a Monnit Gateway via Modbus. The Monnit gateway supports multiple wireless devices. Additional eze System drivers are needed for the individual wireless devices.
Settings (center panel)
Name - The name is up to the user. Our suggestion is to choose a naming convention that makes the viewing the device list intuitive. Such as referring to the sensor and/or application. Keep the name short as it will be combined with the register name to create the default “Field” name (if added to “Fields”)
Active Check box - Check this box and “Save changes” to run the driver. The driver program can be suspended by unchecking the box and clicking on “Save changes”.
User Notes - This space can be used to store information specific to the device and your application, such as: location, wiring, scaling, etc.
eze System Notes - In this space we provide: wiring instructions, product image, product details.
Modbus address - Enter Device I.D. (Modbus address). Default address is 95. This address must be unique on the bus.
Registers
# | Name | Unit | Description |
---|---|---|---|
1 | Gateway serial | . | Unique serial number |
2 | Devices (Active) | . | Number of registered sensors active |
3 | Devices (Configured) | . | Number of registered sensors configured to operate through the gateway |
4 | Operating channel | . | Wireless channel in use 0-25 |
5 | Uptime | s | |
6 | Active | . | |
7 | Full reset | . | |
8 | Network reset | . |
Notes
Gateway for connecting Monnit wireless devices Connect: ezeio D0 -> Gateway D- (green) ezeio D1 -> Gateway D+ (orange) ezeio +V -> Gateway V+ (red) ezeio 0V -> Gateway GND (black) Make sure gateway "SELECT" jumper is OFF. Gateway factory defaults to 19200/N/8/1 Default address 95