Manufacturer: Carlo Gavazzi
Product: Series 20
Model: EM21/EM24
Class: MODBUS
Updated: 2023-11-13

[ CLICK HERE FOR MORE INFORMATION ]


Registers

#NameUnitDescription
1Total Net EnergykW hBidirectional, Active, Resettable
2Total Positive EnergykW hPositive, Active, Resettable
3Total Negative EnergykW hNegative, Active, Resettable
4Total PowerkWTotal, Active
5Avg Volt L-NVLine-to-Neutral
6Avg Volt L-LVLine-to-Line
7FrequencyHz
8Avg Power FactorAverage
9Current ph AAPhase A
10Current ph BAPhase B
11Current ph CAPhase C
13Energy ph AkW hBidirectional, Active, Phase A
14Energy ph BkW hBidirectional, Active, Phase B
15Energy ph CkW hBidirectional, Active, Phase C
16Power ph AkWActive, Phase A
17Power ph BkWActive, Phase B
18Power ph CkWActive, Phase C
19Volt A-NVRMS
20Volt B-NVRMS
21Volt C-NVRMS
22Volt A-BVRMS
23Volt B-CVRMS
24Volt C-AVRMS
25Power Factor ph A
26Power Factor ph B
27Power Factor ph C
42Total Reactive PowerkVARBidirectional
43Reactive Power ph AkVARBidirectional, Phase A
44Reactive Power ph BkVARBidirectional, Phase B
45Reactive Power ph CkVARBidirectional, Phase C
46Total Apparent PowerkVARBidirectional
47Apparent Power ph AkVARBidirectional, Phase A
48Apparent Power ph BkVARBidirectional, Phase B
49Apparent Power ph CkVARBidirectional, Phase C

Notes

Three phase electric energy meter

Comm wiring:
  #41 = D0
  #42 = D1
  #43 = com

EM2x is fixed at 9600 bps