ezeio2:driverdetail

Manufacturer: Produal
Product: PEL
Model: PEL-M
Class: MODBUS
Updated: 2024-06-27

[ CLICK HERE FOR MORE INFORMATION ]


Description

This driver is design to allow communication with the Produal PEL via Modbus RTU.


Name - The name is up to the user. Our suggestion is to choose a naming convention that makes the viewing the device list intuitive. Such as referring to the sensor and/or application. Keep the name short as it will be combined with the register name to create the default “Field” name (if added to “Fields”)

Active Check box - Check this box and “Save changes” to run the driver. The driver program can be suspended by unchecking the box and clicking on “Save changes”.

User Notes - This space can be used to store information specific to the device and your application, such as: location, wiring, scaling, etc.

eze System Notes - In this space we provide: wiring instructions, product image, product details.


Modbus address - Enter Device I.D. (Modbus address). This address must be unique on the bus.

Registers

#NameUnitDescription
1Pressure measurementPaPressure differential expressed in Pascals
2Time constantsUptime counter 0-60 seconds
3Selected pressure rangePaSelectable ranges 0-7. See manufactures documents
4Measurement output%Percentage of range
5Measurement outputPaMeasurement output

Notes

Differential pressure transmitter for air handling systems.
To set up Modbus: use Produal ML-SER

Connection:
PEL-M (A+) —> ezeio (D1)
PEL-M (B-) —> ezeio (D0)