ezeio2:driverdetail

Manufacturer: Kohler-SDMO
Product: Genset panel
Model: APM303
Class: MODBUS
Updated: 2023-11-13

[ CLICK HERE FOR MORE INFORMATION ]


Registers

#NameUnitDescription
1Gen V L1-NV
2Gen V L2-NV
3Gen V L3-NV
4Gen V L1-L2V
5Gen V L1-L3V
6Gen V L1-L3V
7Gen A L1A
8Gen A L2A
9Gen A L3A
10Gen kW TotalkW
11Gen kVA TotalkVA
12Gen PFpf
13Gen kW L1kW
14Gen kW L2kW
15Gen kW L3kW
16Gen kW L1 (Effective)kW (E)
17Gen kW L2 (Effective)kW (E)
18Gen kW L3 (Effective)kW (E)
19Gen PF L1pf
20Gen PF L2pf
21Gen PF L3pf
22Load Character (R/L/C)(R/L/C)
23RPMrpm
24Gen FreqHz
25Power precision
26Battery VV
27BIN
28BOUT
29Oil pressurepsi
30Coolant temp°C
31Fuel level%
32Unit systemM/US
33D plusV
34Total active energykWh
35Maintenance timerh
36Start counter
37Genset serial
38SW version
39SW patch version
40Running hoursh
41Nominal currentA
42Connection type
43Remote control
44Status
45Warnings
46Errors
47Signals
48Common

Notes

Genset control panel for engines without J1939.

Default address is '5'
Default speed is 9600 bps

ezeio D0 -> APM303 A-485
ezeio D1 -> APM303 B-485
ezeio C -> APM303 COM-485

**CAUTION**
APM303 scaling is poorly documented, and may change for unknown reasons. Make sure to set the scaling manually, and check it for correctness.

  • ezeio2/driverdetail.txt
  • Last modified: 2024-05-07 23:25
  • by andreh