ezeio2:indicators:start

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Next revision
Previous revision
ezeio2:indicators:start [2019-09-02 19:13] – created andrehezeio2:indicators:start [2023-10-23 23:27] (current) – [Normal operation] andreh
Line 49: Line 49:
 === The SERVER indicator === === The SERVER indicator ===
  
-| {{ :ezeio2:off.gif?nolink |}} | OFF | No connection to server. Logic is not active. |+| {{ :ezeio2:rfast.gif?nolink |}} | fast RED blink | No connection to server. Logic is not active. |
 | {{ :ezeio2:red.gif?nolink |}} | RED | No connection to server. Logic is running. | | {{ :ezeio2:red.gif?nolink |}} | RED | No connection to server. Logic is running. |
-| {{ :ezeio2:rg.gif?nolink |}} | RED - GREEN | Connected to server. Logic is not active. |+| {{ :ezeio2:gfast.gif?nolink |}} | fast GREEN blink | Connected to server. Logic is not active. |
 | {{ :ezeio2:green.gif?nolink |}} | GREEN | Connected to server. Logic is running. | | {{ :ezeio2:green.gif?nolink |}} | GREEN | Connected to server. Logic is running. |
  
 It is normal that the server LED will flicker while green. This indicates normal communication activity. It is normal that the server LED will flicker while green. This indicates normal communication activity.
  
 +==== Button function during startup ====
  
 +The button on the ezeio can be used to override normal startup.
 +
 +== DEFAULT COMMUNICATION SETTINGS ==
 +
 +To force default communication settings (Ethernet DHCP and default cell modem settings), simply hold the button while power is applied, and keep holding the button until the LED startup roll is finished. Then release the button.
 +This will also prevent any scripts and drivers to run.
 +
 +The ezeio will revert to the programmed settings after the next reset.
 +
 +== KNOWN/FIXED ETHERNET IP ==
 +
 +The Ethernet IP setting can be forced to 192.168.1.77 by holding the button when power is applied, but release the button during the LED startup roll. This only affects the Ethernet IP address. All other functions operate as normal.
 +
 +The ezeio will revert to the programmed settings after the next reset.
 +
 +== HALT SCRIPTS AND DRIVERS ==
 +
 +By pushing down the button during the startup roll, and holding it until the roll completes, the ezeio will start without running any scripts or drivers. The scripts can be started again by pushing the button once, or by restarting the ezeio.
 +
 +== STOPPING SCRIPTS DURING RUNTIME ==
 +
 +The scripts and drivers can be stopped any time during runtime by clicking the button twice. To restart the scripts and drivers, push the button once. If the ezeio is restarted the scripts will still start normally.
  