 **REGISTER 1 & 2 modes** - Each discrete input is duplicated, providing the opportunity apply two modes of initial processing and two methods of scaling. The ezeio controller's microprocessor reads the onboard inputs at a rate of 1000 times per second and exports the results every 1/10 of a second (//connected I/O Expander inputs are sampled slower as they are transmitted via CANbus//). Additional processing is applied to logged registers (see [[ezeio2:userinterface:configuration:fields|"Fields"]]) **REGISTER 1 & 2 modes** - Each discrete input is duplicated, providing the opportunity apply two modes of initial processing and two methods of scaling. The ezeio controller's microprocessor reads the onboard inputs at a rate of 1000 times per second and exports the results every 1/10 of a second (//connected I/O Expander inputs are sampled slower as they are transmitted via CANbus//). Additional processing is applied to logged registers (see [[ezeio2:userinterface:configuration:fields|"Fields"]])
  
-**Register 1 & 2 modes** - Choose one of the setting below for registers 1 & 2.+**Register 1 & 2 modes** - These modes control how the analog to digital converter calculates the live values. //Separate settings on the individual "Field" settings control how each channel is logged//.  Choose one of the setting below for registers 1 & 2.
  
 | **Mode** | **Description** | **Effect** |  | **Mode** | **Description** | **Effect** | 
Line 107: Line 107:
  
 === Available registers === === Available registers ===
 +
 +| 1 | Raw electrical value | Unit type is set by "Input hardware type", V, mA, Ohm |
 +| 2 | Raw electrical value | Unit type is set by "Input hardware type", V, mA, Ohm |
 +| 3 | Scaled value, Register 1 | Scaled by 2 point calibration | 
 +| 4 | Scaled value, Register 2 | Scaled by offset and factor |
 +| 5 | Logical state | Analog value converted to digital (on/off) based on threshold setting |
 +| 6 | Logical cycles | Number of times "Logical state" changes from off to on |
 +| 7 | Logical active time | Number of seconds logical state is "on" (runtime) | 
 + 