Differences
This shows you the differences between two versions of the page.
Both sides previous revision Previous revision Next revision | Previous revision | ||
ezeio2:userinterface:configuration:devices:driverlist:discretein [2022-06-22 00:38] – johpar | ezeio2:userinterface:configuration:devices:driverlist:discretein [2024-05-09 23:07] (current) – removed andreh | ||
---|---|---|---|
Line 1: | Line 1: | ||
- | ==== Discrete Input driver ==== | ||
- | === Description === | ||
- | |||
- | This driver (located in the Core drivers folder) is designed for use with the ezeio MkII controller and the ezeio MkII I/O Expander. It is ideal for reading resistance (Ohms), and sensors with DC current (0-30 mA) or voltage (0-10 VDC) signals. // This driver does support pulse outputs and thermistors, | ||
- | |||
- | ---- | ||
- | |||
- | {{: | ||
- | |||
- | === Settings === | ||
- | |||
- | **Name** - The name is up to the user. Our suggestion is to choose a naming convention that makes the viewing the device list intuitive. Such as referring to the sensor and/or application. Keep the name short as it will be combined with the register name to create the default " | ||
- | |||
- | **Notes** - This space can be used to store information specific to the device, such as: location, wiring, scaling, etc. | ||
- | |||
- | **Active** Check box - Check this box and "Save changes" | ||
- | |||
- | {{: | ||
- | |||
- | **Device** - Select the ezeio controller or the device number of a connected ezeio I/O Expander. | ||
- | |||
- | **Input number** - Select the input number (1-8) of the selected device. | ||
- | |||
- | {{: | ||
- | |||
- | **Input hardware type** - Select the type of sensor or signal type (0-10V, 0-30mA (4-20mA), Ohms, thermistor). Some of the thermistor choices are tailored to specific sensors and others are generic (see the table below for details). Options from pulse are shown, but we recommend using the "Pulse input" driver. //The Self test is diagnostic setting to test the circuitry of the input when nothing is connected// | ||
- | |||
- | |||
- | |||
- | **REGISTER 1 & 2 modes** - Each discrete input is duplicated, providing the opportunity apply two modes of initial processing and two methods of scaling. The ezeio controller' | ||
- | |||
- | **Register 1 & 2 modes** - Choose one of the setting below for registers 1 & 2. | ||
- | |||
- | | **Mode** | **Description** | **Effect** | | ||
- | | Snapshot | Captured value is a single sample | 99 samples are rejected | | ||
- | | Minimum | Lowest of the 100 readings over sample interval | 99 samples are rejected | | ||
- | | Maximum | Highest of the 100 readings over sample interval | 99 samples are rejected | | ||
- | | Average | Average of the 100 readings over sample interval | All samples used to find avg. | | ||
- | | Pulse rate | Rate is shown as frequency (Hz x 1000) | | | ||
- | | Pulse count | Counting total number of pulse | | | ||
- | | Pulse interval | milliseconds elapsed since last pulse | | | ||
- | | Differential pulse count | | | | ||
- | |||
- | |||
- | **SCALING OF REGISTER 1** - Register 1 can be scaled to a unit value such as PSI or LPM with a 2 point linear conversion method. A rough conversion can be obtained by entering corresponding values from a table supplied by the sensor manufacture. For a calibrated conversion, use a trusted gauge or probe to provide readings at two points within the sensors range. Enter the value for one point and use the driver' | ||
- | |||
- | {{: | ||
- | |||
- | **Raw value point A & B** - By default, the range shown here is set based on the "Input hardware type" selected, such as 0-10V (0.0 - 10.0) or 0-30mA (4.0 - 20.0). This would correlate to the full scale of a typical sensor. These fields can be changed if required to match the output of your sensor or the scale range you wish to use in the next step. | ||
- | |||
- | **Scaled value at point A & B** - Enter values here that correlate to the Min/Max raw values. For example: 4.0mA = 0 psi and 20.0mA = 250 psi | ||
- | |||
- | **Low error - High error** - Enter values here that represent the normal range for the application. This could also represent the operating range of the sensor, so a negative value could indicate an open circuit. When the value is out of this range, the " | ||
- | |||
- | **SCALING OF REGISTER 2** - This register' | ||
- | |||
- | **Offset** - Set a starting point or floor for the scaling such as 4 in the case of 4-20mA signals. | ||
- | |||
- | **Factor** - Multiply the raw value to create a linear conversion that matches your sensors scale. To find the factor, divide the sensor full scale range by the number of raw unit steps. | ||
- | |||
- | **LOGIC STATE** - This feature converts any ranging analog value into a digital value (or boolean) by defining a threshold beyond which it is consider true (represented by 1, or 100). | ||
- | |||
- | **Threshold (Scaled)** - Enter a threshold value above or below which the state should be considered true (or ON). | ||
- | |||
- | **Filter time** - Filter out transient value changes by entering a number of seconds (and tenths) in this field. The value must then exceed the threshold for the proscribed time before it is considered true. | ||
- | |||
- | **Logic** - Set the true (or ON) state to be above or below the threshold value, with a value of 1 or 100. Choosing 100, make it easy to use the value to drive a digital output via " | ||
- | |||
- | ==== Thermistor options ==== | ||
- | |||
- | <WRAP center round tip 60%> | ||
- | For thermistors, | ||
- | </ | ||
- | |||
- | |||
- | | **Thermistor Name** | **Source or Generic** | **Part #** | **Application** | **Range** | | ||
- | | 10k type II | Generic | -- | | | ||
- | | 10k type III | Generic | -- | | | ||
- | | 10k type B=3380 | eze System | BA0010 | | | ||
- | | 2k2 | eze System | BA0022 | | | ||
- | | 100k | Generic | -- | | | ||
- | | TX1001 Pro | ThermoWorks | TX-1001X-OP | | | ||
- | | ET7273 | | ET7273 | | |