ezeio2:userinterface:configuration:devices:driverlist:discretein [2023-10-13 17:23] – [Status & Registers (right panel)] johparezeio2:userinterface:configuration:devices:driverlist:discretein [2023-10-13 18:02] johpar
Line 33: Line 33:
 **REGISTER 1 & 2 modes** - Each discrete input is duplicated, providing the opportunity apply two modes of initial processing and two methods of scaling. The ezeio controller's microprocessor reads the onboard inputs at a rate of 1000 times per second and exports the results every 1/10 of a second (//connected I/O Expander inputs are sampled slower as they are transmitted via CANbus//). Additional processing is applied to logged registers (see [[ezeio2:userinterface:configuration:fields|"Fields"]]) **REGISTER 1 & 2 modes** - Each discrete input is duplicated, providing the opportunity apply two modes of initial processing and two methods of scaling. The ezeio controller's microprocessor reads the onboard inputs at a rate of 1000 times per second and exports the results every 1/10 of a second (//connected I/O Expander inputs are sampled slower as they are transmitted via CANbus//). Additional processing is applied to logged registers (see [[ezeio2:userinterface:configuration:fields|"Fields"]])
  
-**Register 1 & 2 modes** - Choose one of the setting below for registers 1 & 2.+**Register 1 & 2 modes** - These modes control how the analog to digital converter calculates the live values. //Separate settings on the individual "Field" settings control how each channel is logged//.  Choose one of the setting below for registers 1 & 2.
  
 | **Mode** | **Description** | **Effect** |  | **Mode** | **Description** | **Effect** | 
Line 108: Line 108:
 === Available registers === === Available registers ===
  
-  - Raw electrical signal +Raw electrical value | Unit type is set by "Input hardware type", V, mA, Ohm | 
-  Raw electrical signal +Raw electrical value | Unit type is set by "Input hardware type", V, mA, Ohm | 
-  Scaled value, Register 1 +Scaled value, Register 1 | Scaled by 2 point calibration |  
-  Scaled value, Register 2 +Scaled value, Register 2 | Scaled by offset and factor | 
-  Logical state +Logical state | Analog value converted to digital (on/off) based on threshold setting | 
-  Logical cycles +Logical cycles | Number of times "Logical state" changes from off to on | 
-  Logical active time+Logical active time | Number of seconds logical state is "on" (runtime) |