Returns information of a given alarm.
ai(3, AL_HOLDOFF)
Returns the remaining holdoff time for alarm #3.
alarmno | Alarm number |
mode | What information is requested |
AL_STATE | The alarm state (1=in alarm, 0=not in alarm) |
AL_HOLDOFF | The remaining time on the holdoff timer (in seconds) |
AL_ALARMHOLDOFF | The alarm holdoff setting (in seconds) |
AL_RESTOREHOLDOFF | The restore holdoff setting (in seconds) |
AL_ISALARM | Returns 1 if the alarm condition is true. Otherwise 0 |
AL_ISRESTORE | Return 1 if the restore condition is true. Otherwise 0 |
AL_RETRIGCOUNT | Number of times the alarm has be re-triggered |
AL_RETRIGDELAY | Time remaining on the alarm retrigger delay (in seconds) |
AL_RETRIGCOUNTSET | Retrigger count configured |
AL_RETRIGDELAYSET | Retrigger delay configured (in seconds) |
This function returns information about the alarm based on the mode parameter
ai(3, AL_RETRIGCOUNT)
[command available in firmware 201008 and later]